Description
The TT-9 Firefighting Water Mist Turbine is an electric-driven stationary fire protection module developed by Rohre®, a brand of THINKTANK Group. Designed for industrial environments such as recycling yards, chemical plants, and oil & gas facilities, it combines fine water-mist technology with a high-power electric turbine to project atomized water over long distances while using far less water than conventional systems.
Its dual-circuit design allows independent or combined operation: a central monitor delivers a powerful full-jet or umbrella stream up to 2,300 L/min, while an outer nozzle ring produces a fine mist up to 400 L/min for efficient cooling and smoke suppression. Both circuits can work separately or together for flexible firefighting strategies.
With 360° rotation, −19° to +43° tilt range, and multi-mode control (automatic via CAN-bus, manual, or remote), the TT-9 ensures precise and responsive operation. Internal heating supports reliable winter performance, and all wetted parts are compatible with water, foam, or water-foam mixtures.
Supplied as an OEM component without FM/UL certification, the TT-9 can be integrated into certified stationary systems under your own brand. Backed by THINKTANK Group’s engineering expertise, Rohre delivers an advanced, low-maintenance, and integration-ready turbine solution for modern fire suppression systems.
Parameter | TT-9 Water Mist Turbine |
---|---|
Water flow range | 100 – 4,000 L/min (mode-dependent) |
Central monitor flow | up to 2,300 L/min |
Mist ring flow | up to 400 L/min |
Rotation (swing) | 360° continuous |
Tilt (elevation) | −19° to +43° |
Supply voltage | 400 V (3-phase) |
Nominal current | max. 29 A |
Drive / propeller | Electric turbine fan (approx. 12.5 kW) |
Media | Water / foam / water-foam mix |
Winterization | Internal heating |
Approx. weight | ~1,000 kg |
Note: operates at standard fire-water pressure; nozzle heads/monitors selectable. Specs can be tailored for OEM projects.