TT-9 Firefighting Water Mist Turbine

A next-generation stationary fire protection module that combines the long-range power of a firefighting monitor with the cooling efficiency of water mist. The TT-9 Electric-driven Firefighting Water Mist Turbine delivers 360° coverage, dual-circuit operation, and fully automatic control—ideal for OEM integration into certified fire suppression systems.

Description

The TT-9 Firefighting Water Mist Turbine is an electric-driven stationary fire protection module developed by Rohre®, a brand of THINKTANK Group. Designed for industrial environments such as recycling yards, chemical plants, and oil & gas facilities, it combines fine water-mist technology with a high-power electric turbine to project atomized water over long distances while using far less water than conventional systems.

Its dual-circuit design allows independent or combined operation: a central monitor delivers a powerful full-jet or umbrella stream up to 2,300 L/min, while an outer nozzle ring produces a fine mist up to 400 L/min for efficient cooling and smoke suppression. Both circuits can work separately or together for flexible firefighting strategies.

With 360° rotation, −19° to +43° tilt range, and multi-mode control (automatic via CAN-bus, manual, or remote), the TT-9 ensures precise and responsive operation. Internal heating supports reliable winter performance, and all wetted parts are compatible with water, foam, or water-foam mixtures.

Supplied as an OEM component without FM/UL certification, the TT-9 can be integrated into certified stationary systems under your own brand. Backed by THINKTANK Group’s engineering expertise, Rohre delivers an advanced, low-maintenance, and integration-ready turbine solution for modern fire suppression systems.

Firefighting Turbine

Parameter TT-9 Water Mist Turbine
Water flow range 100 – 4,000 L/min (mode-dependent)
Central monitor flow up to 2,300 L/min
Mist ring flow up to 400 L/min
Rotation (swing) 360° continuous
Tilt (elevation) −19° to +43°
Supply voltage 400 V (3-phase)
Nominal current max. 29 A
Drive / propeller Electric turbine fan (approx. 12.5 kW)
Media Water / foam / water-foam mix
Winterization Internal heating
Approx. weight ~1,000 kg

Note: operates at standard fire-water pressure; nozzle heads/monitors selectable. Specs can be tailored for OEM projects.